Can a tankless water heater run two showers at once?
Yes, if it is sized for it. Two 2.1 GPM showers need 4.2 GPM of hot water. With 50°F water coming in and a 120°F setting, that takes a 160,000 BTU condensing gas unit; in the cold North, where winter water arrives near 40°F, 199,000 BTU. A heater sized for one shower will run the second one cold.
What size tankless water heater do I need for a family of 4?
A family of four usually peaks at two showers at once, 4.2 GPM. That takes a 160,000 BTU condensing gas unit where winter water comes in at 50°F, and 199,000 BTU where it comes in at 40°F. Tankless heaters are sized by flow at your temperature rise, not by the number of people or bathrooms.
Does a gas tankless water heater need electricity?
Yes. A gas tankless water heater burns gas for heat but needs 120 V electricity to light the burner, run the combustion fan and work the controls. The draw is small: the RU199i, a 199,000 BTU Rinnai, uses 84 W while heating, 1.3 W on standby and up to 148 W when its freeze protection runs. With the power off it will not fire, so a power cut means no hot water.
What size breaker for a tankless water heater?
Use the breakers in the installation manual. Whole-house electric tankless heaters split their load across two to four 240 V circuits, each on a 40 or 50 A double-pole breaker. Rheem’s 18 kW RTEX-18 draws 75 A and takes 2 × 40 A breakers; a 36 kW unit draws 150 A and takes 4 × 40 A (RTEX-36) or 3 × 50 A (Stiebel Eltron Tempra 36). For the total amps, divide the watts by 240.